EasyManua.ls Logo

Hach POLYMETRON 9135 - Page 54

Hach POLYMETRON 9135
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Transmitter 9135 - pH/redox measurement
Page 50
S1 & S2 RELAYS
Proportionality coefficient : slope of regulation.
COEF.XP1/2 : XXX In %
Value of the pulse width (0,1 < T < 0,7) :
T1/2 : XXX In %
Minimum number of pulses per minute. Program
this value according to the control system
associated to the relay :
MIN : XXX In i/min
Maximum number of pulses per minute. Program
this value according to the control system
associated to the relay.
MAX : XXX In i/min
MANUAL MODE
Force relay S1 or S2. Pressing the function key
associated to the relay, the relay is activated till
you release the key. The corresponding icon is
displayed according to the relay state.
PULSE CONTROL :
The pulse period is constant and programmable (3
to 60 s). It is the cycle quotient (α) which varies
according to the sample pH value.
Off
On
"
?
"
?
"
?
S3
T T T
COEF.XP1 : 100%
T1 : 2.00 s
MIN : 001 i/min
MAX : 200 i/min
RELAY S1
Select
COEF.XP2 : 100%
T2 : 2.00 s
MIN : 001 i/min
MAX : 200 i/min
RELAY S2
Select
7.00
pH
25.0 °C
CONTROLLER
S2 S1
Tps
Time

Table of Contents