136
Failure code
Outdoor 
digital 
display tube: 
122-0, 1
Indoor wired 
controller: 7A
Indoor unit LED status
LED5 Failure description: 
Radiator temp. sensor of compressor mo-
dule is abnormal.
20 times
Outdoor unit LED status
LED1L ED2
Normal Normal
1. Model Failure diagnosis and troubleshooting
MRV 5-HR series 
DiagnosisT roubleshooting
2. Abnormity detection method
◆
 Check if the temperature 
acquisition circuit of inverter 
board is normal.
◆
 Check if the resistance of 
temperature sensor is normal.
◆
 Check if they are connected 
correctly
conditions
The temperature sensor is 
disconnected or the resistance 
is incorrect.
4. Possible causes
◆
 The resistance of 
temperature sensor is found 
with drift.
◆
 The inverter board acquires 
inaccurate temperature.
Check if the sensor and 
variable frequency board is 
connected correctly.
Check if the sensor 
resistance is normal.
Replace  t he  variabl e 
frequency board.
Replace the sensor.
Adjust the connection 
between temperature sensor 
and variable frequency 
board.
Y
Y
N
N