136
Failure code
Outdoor
digital
display tube:
122-0, 1
Indoor wired
controller: 7A
Indoor unit LED status
LED5 Failure description:
Radiator temp. sensor of compressor mo-
dule is abnormal.
20 times
Outdoor unit LED status
LED1L ED2
Normal Normal
1. Model Failure diagnosis and troubleshooting
MRV 5-HR series
DiagnosisT roubleshooting
2. Abnormity detection method
Check if the temperature
acquisition circuit of inverter
board is normal.
Check if the resistance of
temperature sensor is normal.
Check if they are connected
correctly
conditions
The temperature sensor is
disconnected or the resistance
is incorrect.
4. Possible causes
The resistance of
temperature sensor is found
with drift.
The inverter board acquires
inaccurate temperature.
Check if the sensor and
variable frequency board is
connected correctly.
Check if the sensor
resistance is normal.
Replace t he variabl e
frequency board.
Replace the sensor.
Adjust the connection
between temperature sensor
and variable frequency
board.
Y
Y
N
N