137
 
Failure code
Outdoor 
digital display 
tube: 
123-0, 1
Indoor wired 
controller: 78, 
7B
Indoor unit LED status
LED5 Failure description: 
Hardware instantaneous over current of the 
20 times
Outdoor unit LED status
LED1 LED2
Normal Normal
1. Model Failure diagnosis and troubleshooting
MRV 5-HR series 
DiagnosisT roubleshooting
2. Abnormity detection method
◆
 Check the module is normal, 
there is short circuit between P, 
N, U, V, W 
◆
 Check whether the module 
good;
◆
 Check the compressor 
resistance is normal,
◆
 Check if the wiring of 
compressor UVW is correct, 
frequency converter board and 
module board connection is 
reliable.
conditions
Hardware instantaneous over 
side
4. Possible causes
◆
 Poor radiating caused the 
module burned;
◆
 The module is punctured to 
cause a breakdown;
◆
 Compressor winding 
resistance too large
◆
UVW wiring short circuit, or 
compressor line short circuit to 
ground
◆
The compressor has a liquid 
shock, causing starting current 
or operating current too high
Check if the supply voltage is normal
Check if the electrical box connect 
correctly, compressor wires connect 
reliably
Check if the inverter module is normal
If the resistance, insulation of the 
compressor is normal
Solve the failure
Reconnect  o r  re-fix  i t  in 
accordance  with  c ircuit  
diagram.
Replace the inverter module 
Replace the compressor
Adjust the power supply.
Y
Y
Y
Y
N
N
N
N
If there are other failures 112,114
Y