253
<Table 2> Dimensions (mm) of connection tube of the indoor units
Indoor (×100W) Gas pipe (mm) Liquid pipe (mm)
7.5~9.5(22~28) 3/8(9.52)×0.8 1/4(6.35)×0.8
12.3~19.1(36~56) 1/2(12.7)×0.8 1/4(6.35)×0.8
24.2~38.2(71~112) 5/8(15.88)×1.0 3/8(9.52)×0.8
Note:
High wall 0.8/1HP gas pipe: Ø12.7
High wall 2HP gas pipe/liquid pipe: Ø15.88/Ø9.52
<Table 3>  Dimensions (mm) of connection pipe of the vale box
Pipe connection
Type of valve 
box for switch 
between cooling 
and heating
Pipe dimensions (OD × minimum wall thickness)
High pressure gas 
pipe
Suction gas pipe
Liquid pipe at the 
outdoor unit side
Gas pipe of 
the indoor unit
Liquid pipe at 
the indoor unit 
side
VP4-450B 1-1/8
(
28.58)×1.2 1-1/8
(
28.58)×1.2 5/8(15.88)×1.0 5/8(15.88)×1.0 3/8(9.52)×0.8
(*1) Refer to the eld pipe
(*2) Please use the are nut installed on the product body again.
Note: 
During  installation, please  conrm the HP gas pipe and Suction gas pipe between outdoor and valve box (such as 
by sending nitrogen into the HP gas pipe and Suction gas pipe), then connect Suction gas pipe to the Suction gas 
pipe of valve box, HP gas pipe to the HP gas pipe of valve box.
(Note): 
When a 072, 092 indoor unit is connected in the downstream, please use the auxiliary 
pipe 
-1,2 for connection according to Fig.11.
When a 122, 162, 182  indoor unit is connected in the downstream, please use the auxiliary pipe  -1,3 for 
connection according to Fig.11.
When  a  High wall 0.8/1HP  indoor  unit  is  connected  in  the  downstream,  please  use  the  auxiliary  pipe  -1,3 f
or connection according to Fig.11.         
When an High wall 2HP indoor unit is connected in the downstream, do not use the auxiliary pipe.