Technical Manual VERSION 2.0 -10-18-2018
4
2.2 Compressor specifications
a. RC2A
MODEL
COMPRESSOR MOTOR
Lubricant
charge
Oil
Heater
Hydrostatic
Pressure
Test
WEIGHT
60 / 50Hz
Rated
Speed
60 / 50Hz
VI
Cap. Control (%)
Type
Hp
Starting
Voltage (V)
Insulation
Protection
m
/hr STEP STEPLESS
60Hz
50Hz
60Hz
50Hz
L W Kg/cm2G
kg
RC2100A
118/98
3550/2950
2.2
2.6
3.5
4.8
33, 66, 100 33~100
3 Phase, 2 Pole, Squirrel Cage, Induction Motor
23
19
Y△
△△
△
PWS
DOL
208
220
230
380
440
460
480
575
380
400
415
Class F
PTC Protection
7
150/300
42
275
RC2140A
165/137 33, 66, 100 33~100 32
26
7 280
RC2180A
216/180 33, 66, 100 33~100 42
35
7 300
RC2200A
233/193 25, 50, 75, 100
25~100 45
37
8 420
RC2230A
277/230 35, 50, 75, 100
35~100 53
44
14 540
RC2260A
309/257 25, 50, 75, 100
25~100 59
49
14 545
RC2300A
352/293 25, 50, 75, 100
25~100 67
56
16 590
RC2310A
371/308 35, 50, 75, 100
35~100 71
59
16 575
RC2320A
384/320 25, 50, 75, 100
25~100 72
60
16 595
RC2340A
407/339 35, 50, 75, 100
35~100 77
64
16 600
RC2370A
440/366 35, 50, 75, 100
35~100 84
70
16 610
RC2410A
490/407 25, 50, 75, 100
25~100 93
78
380
440
460
480
575
16 730
RC2430A
509/423 25, 50, 75, 100
25~100 93
78
16 735
RC2470A
567/471 25, 50, 75, 100
25~100 108
90
18 800
RC2510A
611/508 35, 50, 75, 100
35~100 117
98
20 760
RC2550A
660/549 25, 50, 75, 100
25~100 126
105
23 820
RC2580A
702/583 35, 50, 75, 100
35~100 131
109
20 805
RC2620A
745/619 35, 50, 75, 100
35~100
137
114
Y△
△△
△
DOL
23 850
RC2710A
858/713 35, 50, 75, 100
35~100 158
131
28 1099
RC2790A
952/791 30, 50, 75, 100
30~100 175
146
28 1140
RC2830A
993/825 30, 50, 75, 100
30~100 183
152
28 1150
RC2930A
1117/929 35, 50, 75, 100
35~100 212
176
28 1180
RC21020A
1223/1017 25, 50, 75, 100
25~100 227
189
40 1500
RC21130A
1350/1122 25, 50, 75, 100
25~100 248
206
40 1520
RC21270A
1521/1268 25, 50, 75, 100
25~100 286
238
53 2100
RC21530A
1847/1539 25, 50, 75, 100
25~100 331
275
53 2200
Nominal Horse Power:
All the above Nominal Hp’s are not equal to the maximum compressor Hp. Please refer to Hanbell selection software’s
output for rated current and Maximum Continuous CurrentM.C.C according to various operating conditions while
selecting sizes of contactor, cable, fuse and wire, etc