EasyManua.ls Logo

Hanbell RC2-930A - Parallel System Applications; Oil Pump Application; Important Note of Applications of Compressor

Default Icon
84 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Manual VERSION 2.0 -10-18-2018
75

7.4 Oil pump application
An additional oil pump is recommended to install to the system when the differential pressure of oil pressure and
suction pressure is less than 4bar ( for example: water cooled flooder chiller). If compressor is operating at the
mentioned condition, the failure of modulation and lubrication will be happened and will seriously damage the
compressor. Besides the installation of additional oil pump, a high low pressure differential switch is also
recommended to install to this kind of system. Please contact with Hanbell for more detailed information of oil pump.
Figure 72 Additional oil pump
Item
Description Item
Description Item
Description
1 Oil pump 5 Solenoid valve 9 External oil separator
2 Compressor 6 Flow switch 10 Service valve
3 Check valve 7 Oil filter cartridge
4 Sight glass 8 Oil cooler
7.5 Important note of applications of compressor
1. Pump down
Do not pump down the compressor on the chiller as a routine operation except only for temporary maintenance or a
long term shut down. Because pump down will cause extremely high temperature in the compression chamber and
overheat of the motor as well due to less amount of refrigerant in the suction side. When doing the pump down, be
sure to take notice of the items listed below :
a. Pump down should be done once each time, as it may be dangerous to the compressor, compression chamber for
pumping down repeatedly.
b. The minimum suction pressure when doing the pump down should be over 15 psig for R134a and 25 psig for R22.
c. Take notice of compressor running noise. If there is any abnormal noise happened, then emergently stop the pump
down.
2. Long term partial load operation
If compressors have to run at partial load below 50% continuously, though maybe within operation limits under such
operation condition and with temperature of motor below trip setting for overheating, insufficient dissipation of heat in
motor will occur due to lower flow rate of suction gas at partial load. If compressors operate under high temperature for
a long time, insulation of motor will deteriorate gradually at risk of serious motor damage finally. In such severe
operation conditions, Hanbell strongly recommends installation of liquid injection system to cool motor coil and use of
Pt100 or Pt1000 sensor as described in chapter 4.4s, to effectively control temperature of motor while running. It is
suggested to switch on liquid injection when temperature of motor coil is higher than 60 and turn off liquid injection
when it’s lower than 50 .
3. Low pressure receiver
When a compressor operates in the following application conditions, installation of a low pressure receiver is
recommended in order to prevent massive liquid refrigerant from returning to the compressor under momentary
changes of operation condition.
Heat pump Parallel system system with long piping
operating in the low ambient temperature area system heating load varies extremely

Related product manuals