Haskris OPC3-OPC15 - Common Faults and Resolutions

Haskris OPC3-OPC15
46 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 39 of 46
Phone: 001 847 956 6420
Email: service@haskris.com
Fault history: When the screen says NO ALARMS, there are no faults currently. Press the button
to see the fault history if needed.
Start and stop: In the bottom right-hand corner, certain faults will display “Start” or “Stop”. Start
indicates when the fault occurred. Stop indicates when the fault was cleared.
Common Faults
Wording
Explanation
Notes to Resolve
Incoming power fault
Phase monitor detected
improper power
Check the phase monitor in the high voltage electrical box, see the
LED status light and error codes
Low liquid level
Liquid level below liquid level
switch
Check for a leak and add fluid so the level is at the fill line
Pump low pressure
Pressure sensor reading low
on pumping circuit
Confirm pump is primed and check ball valve adjustment
Pump high pressure
Pressure sensor reading high
on pumping circuit
Inspect external piping for a restriction to flow. All external shut off
valves should be fully open. All filters and strainers should be clean.
Pump high amp draw or
Pump motor overload
Pump overload contact opened
Reset alarm, check overload and push reset button if necessary,
measure pump amp draw
High refrig press
Pressure sensor reading high
on a refrigeration circuit
Confirm the fan is spinning and check the condenser for debris or
blockage that could reduce air flow
Low refrig press
Pressure sensor reading low
on a refrigeration circuit
Contact Haskris for diagnostics and troubleshooting
Description of common faults
Log #, higher number is more recent
Description
Time and date stamp
Example fault history screen