XI. Maintenance
Frequency
Schedule: Inspections should happen at least once every 6 months.
Activity: During each inspection, the cleanliness of the water and electrical should be checked.
Secondary Water
Purpose: Maintaining sufficient volume of clean water ensures proper operation of the unit and
consistent cooling for the Canon MRI.
Maintenance: The recommended full water level in the reservoir is the height of the tank’s overflow
drain port. If the level falls, replenish the reservoir as needed until the reservoir remains full. The
water should be free of particles and biological growth. If the water is visibly dirty or contaminated
flush the water from the whole system and refill with fresh drinking/spring water.
Electrical Inspection
Maintenance: Use a multimeter to check electrical values. Take measurements at contactors or
terminal blocks. Compare values to the unit or component name plate.