Connections
• Piping schematic below shows the plumbing connections.
• Drawings below show the location of the fluid connections on the unit.
D = ANTI-VIBRATION JOINTS; SUPPLIED AND INSTALLED BY CUSTOMER / CONTRACTOR.
E = WW / MANIFOLD SUPPLY SIDE BALL VALVES; SUPPLIED WITH WW / MANIFOLD.
F = FLOWMETER (40 GPM, SUPPLIED BY CUSTOMER/CONTRACTOR).
G = WW / MANIFOLD RETURN SIDE BALL VALVES; SUPPLIED WITH WW / MANIFOLD.
H = CITY WATER INLET BALL VALVE; SUPPLIED WITH WW / MANIFOLD.
I = WW / MANIFOLD DRAIN / OVERFLOW CONNECTION; DRAIN VALVE SUPPLIED WITH WW / MANIFOLD (VALVE IS INTERNAL)
J = SHUT OFF VALVE; SUPPLIED AND INSTALLED BY CUSTOMER / CONTRACTOR.
K = PRESSURE REGULATOR (70 PSI MAXIMUM) SUPPLIED AND INSTALLED BY CUSTOMER / CONTRACTOR.
F1 = FILTER SUPPLIED WITH MRI SYSTEM; INSTALLED BY CANON ENGINEER.
F2 = 100 MICRON FILTER SUPPLIED AND INSTALLED BY CUSTOMER / CONTRACTOR.
BFP = BACK FLOW PREVENTER SUPPLIED AND INSTALLED BY CUSTOMER / CONTRACTOR.
NOTE: (1) CITY WATER SHALL NOT EXCEED 55 PSI.
(2) IN THE EVENT OF POWER LOSS OR CHILLER FAILURE CITY WATER WILL PROVIDE COOLING TO THE REFRIGERATOR
COMP CIRCUIT ONLY. WHEN IN CITY WATER BYPASS THE DRAIN MUST BE OPEN.
(3) RF CIRCUIT IS NOT APPLICABLE TO WW3 MODEL