December 2001 Commissioning 6 475
Speed controller Adjusting the speed controller:
7
77
7 Deselect Pass over reference point by setting MP1340 = 0.
7
77
7 Ensure that the loaded PLC program fulfills the following conditions:
Position control loop is closed (W1038/W1040 = 0). If the position
controller is not optimized, error messages appear if the position
controller is closed.
Servo drive controller is enabled (Module 9161)
NC stop is inactive, M4560 = 1
Axis direction buttons active
Axes are clamped
7
77
7 In the MANUAL mode, use the oscilloscope function to select a step
function (approx. 500 mm/min) that will not overdrive the speed controller,
i.e. that does not limit I NOMINAL.
Display the nominal velocity value V (NOM RPM), the actual speed value V
(ACT RPM) and the nominal current value I NOMINAL.
7
77
7 Activate the step function with the axis direction buttons.
7
77
7 To change the machine parameters, press the MP EDIT soft key in the
setup menu.
7
77
7 Increase MP2500.x (P factor) up to the oscillation limit.
MP2500 at the oscillation limit