4 Setpoint
Positioner DC 6-06 21
The correction curve must be parameterized as strictly rising, which means that both x and
y values must increase as the index increases. Inverting filling setpoint over this path is not
permitted. This parameterization is checked by the control unit and in case of error the
configuration error 3000 ConfigurationError = 40 is output. The curve is ignored in this
case.
The actuator setpoint is used on the control loop to trigger the actuator (
8.3.1 Servo
control loop).