11 Parameter description
72 Positioner DC 6-06
11.2 List 1: Parameter
No. Name Meaning
310 ActPosSecureMin
Level: 6
Range: 0..100 %
Page(s): 52
Minim
um control path to protect the actuator from
mechanical and thermal stress (approx. 3 %)
312 ActPosSecureMax
Level: 6
Range: 0..100 %
Page(s): 52
Maxim
um control path to protect the actuator from
mechanical and thermal stress (approx. 97 %)
331 FuelSetpSubst
Level: 4
Range: 0..100 %
Page(s): 25
Equivalent va
lue for the setpoint generator in case of
error
340 AnaStopThresholdLow
Level: 6
Range: 0..100 %
Page(s): 24
Definition of
the lower threshold for the stop request
via analogue input
341 AnaStopThresholdHigh
Level: 6
Range: 0..100 %
Page(s): 24
Definition of
the upper threshold for the stop request
via analogue input
342 AnaStopSensorSubst
Level: 6
Range: 0..100 %
Page(s): 26
Equivalent va
lue for the analogue stop sensor in case of
error
810 FunctStopRequest
Level: 6
Range: 0..5
Page(s): 31
Configuratio
n of the stop request via a digital input
828 FunctErrorReset
Level: 6
Range: -5..5
Page(s): 31
Configuration of the error
reset function via a digital
input
845 FunctAutoAdjust
Level: 6
Range: -5..5
Page(s): 31
Configuratio
n of the auto adjust function via a digital
input
1500 FuelSetPWMIn1RefLow
Level: 4
Range: 0..100 %
Page(s): 35, 36
Lower reference value of PWM input
1 for setpoint
selection