7 Technical data
40 Positioner DC 6-06
7.2 Inputs and Outputs
All inputs and outputs are protected against polarity reversal and short circuit-proof against
battery positive and battery negative.
Pin 1 Position (analogue output) I
a
= 4 .. 20 mA, R
a
= 20
or
Position (PWM output) I
sink
< 0.3 A, ground switching
50..500Hz, external R
pu
required
Pin 2 Stop (analogue input) U = 0..5 V, R
e
= 100 k, f
g
= 15 Hz
or I = 4 .. 20 mA, R
e
= 200 , f
g
= 15 Hz
or
Setpoint (PWM input 1) U
0
< 1 V, U
1
> 5 V, R
pd
= 100 k
50..500Hz
Pin 6 Reference voltage U
ref
= 5 V ±125mV, I
ref
< 30 mA
Pin 7 Setpoint (analogue input) U = 0..5 V, R
e
= 100 k, f
g
= 15 Hz
or I = 4 .. 20 mA, R
e
= 200 , f
g
= 15 Hz
Pin 10 Error lamp (digital output) I
sink
< 0,3 A, ground switching
Pin 11 Stop (digital input) U
0
< 1 V, U
1
> 5 V, R
pd
= 100 k,
optional R
pu/pd
= 4.75 k
or
Setpoint (PWM input 3) U
0
< 1 V, U
1
> 5 V, R
pd
= 100 k,
50..500Hz
Pin 15/16/17 control path measurement internal in the actuator with reference
feedback
Pin 18/19 Actuator solenoid output I < 7 A, I < 11 A for T < 60 s, PWM
CAN H/L CAN communication ISO/DIS 11898, standard/extended
identifier, baud rate up to 1 Mbps
9-pole Serial communication HZM interface up to 57600 baud
Pin 2 and Pin 11 are used alternately as PWM input for the setpoint depending
on whether the stop is induced digitally or analoguely. With an analogue
setpoint this makes no difference.
Note

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Heinzmann PANDAROS DC 6-06 and is the answer not in the manual?

Heinzmann PANDAROS DC 6-06 Specifications

General IconGeneral
BrandHeinzmann
ModelPANDAROS DC 6-06
CategoryValve Positioners
LanguageEnglish