7 Technical data
40 Positioner DC 6-06
7.2 Inputs and Outputs
All inputs and outputs are protected against polarity reversal and short circuit-proof against
battery positive and battery negative.
Pin 1 Position (analogue output) I
a
= 4 .. 20 mA, R
a
= 20
or
Position (PWM output) I
sink
< 0.3 A, ground switching
50..500Hz, external R
pu
required
Pin 2 Stop (analogue input) U = 0..5 V, R
e
= 100 k, f
g
= 15 Hz
or I = 4 .. 20 mA, R
e
= 200 , f
g
= 15 Hz
or
Setpoint (PWM input 1) U
0
< 1 V, U
1
> 5 V, R
pd
= 100 k
50..500Hz
Pin 6 Reference voltage U
ref
= 5 V ±125mV, I
ref
< 30 mA
Pin 7 Setpoint (analogue input) U = 0..5 V, R
e
= 100 k, f
g
= 15 Hz
or I = 4 .. 20 mA, R
e
= 200 , f
g
= 15 Hz
Pin 10 Error lamp (digital output) I
sink
< 0,3 A, ground switching
Pin 11 Stop (digital input) U
0
< 1 V, U
1
> 5 V, R
pd
= 100 k,
optional R
pu/pd
= 4.75 k
or
Setpoint (PWM input 3) U
0
< 1 V, U
1
> 5 V, R
pd
= 100 k,
50..500Hz
Pin 15/16/17 control path measurement internal in the actuator with reference
feedback
Pin 18/19 Actuator solenoid output I < 7 A, I < 11 A for T < 60 s, PWM
CAN H/L CAN communication ISO/DIS 11898, standard/extended
identifier, baud rate up to 1 Mbps
9-pole Serial communication HZM interface up to 57600 baud
Pin 2 and Pin 11 are used alternately as PWM input for the setpoint depending
on whether the stop is induced digitally or analoguely. With an analogue
setpoint this makes no difference.