10 Error handling
Positioner DC 6-06 67
3076 ErrParamStore 3176 SErrParamStore
Cause: An error has occurred while programming the control unit's parameter
memory.
Reaction: - System cannot be started.
- Emergency shutdown.
Action: - Restart control unit with
3.7 Resetting a control unit.
- Notify
HEINZMANN.
3077 ErrProgramTest 3177 SErrProgramTest
Cause: The continuous monitoring of the program memory returned an error.
Reaction: - System cannot be started.
- Emergency shutdown.
Action: - Restart control unit with
3.7 Resetting a control unit.
- Notify
HEINZMANN.
3078 ErrRAMTest 3178 SErrRAMTest
Cause: The continuous monitoring of the main memory (RAM) returned an error.
Reaction: - System cannot be started.
- Emergency shutdown.
Action: - Make a note of the settings of parameters 3895 RAMTestAddrHigh
and
3896 RAMTestAddrLow
- Restart control unit with
3.7 Resetting a control unit.
- Notify
HEINZMANN.
3081 Err5V_Ref 3181 SErr5V_Ref
Cause: The 5V sensor reference voltage 3603 5V_Ref is not within the permitted
range of 4.5 to 5.5 V.
Reaction: - Error message.
- Errors clears itself if the voltage is within the normal range again.
Action: Check the sensor supply.