10 Error handling
Positioner DC 6-06 69
Bit Meaning
0 Program identifier in the E
2
PROM is invalid, the program stays in
the bootloader, start is not possible
1 Operating data memory 2 in the E
1
PROM is invalid, the operating
data are cleared, start is possible
2 Operating data memory 2 in the E
2
PROM is invalid, the operating
data are cleared, start is possible
3 Serial number memory in the E
2
PROM is invalid, start is possible
4 Error memory in the E
2
PROM is invalid, the error memory is
cleared, start is possible
5 Parameter memory in the E
2
PROM is invalid, standard parameters
of the firmware are transferred, start is not possible
6 Exception memory in the E
2
PROM is invalid, start is possible
Action: - Check data for correct settings,
- Restart control unit with
3.7 Resetting a control unit
- Notify
HEINZMANN.
Note: The error only occurs after control unit reset. Bit 5 is signalled after each
program download.
3092 ErrConfiguration 3192 SErrConfiguration
Cause: Configuration error
Reaction: - System cannot be started.
- Control unit operates with standard parameters
Action: - Check configuration for correct settings,
- Restart control unit with
3.7 Resetting a control unit
Reference:
10.6 Configuration error