EasyManua.ls Logo

HiDew DDS - Technical Data: DVS Models (070-230); DVS 070-100 Specifications; DVS 160-230 Specifications

HiDew DDS
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation, use and maintenance manual rev08
DDS-DCS-DVS-DOS - Dehumidifiers for small swimming pools
25 - 60
4.2 DVS TECHNICAL DATA TABLES
MODEL
um
070
090
100
Dehumidification capacity
L/day
67
92
99
Nominal air flow
m
3
/h
600
700
800
Useful static head
Pa
40
40
40
Sound pressure
dB(A)
46
47
48
Hot water coil power
kW
6.1
6.8
7.5
Water coil pressure drops with valve
kPa
33
40
47
Electrical power supply
V/ph/Hz
230/1+N/50
230/1+N/50
230/1+N/50
Electrical heaters capacity
kW
2
3
3
Nominal compressor power
kW
0.85
1.37
1.37
Nominal compressor current
A
3.89
6.37
6.37
Nominal unit power
kW
0.93
1.47
1.51
Maximum unit power
kW
1.36
2.02
2.02
Nominal unit current
A
4.6
7.1
7.5
Maximum unit current
A
6.6
9.7
9.7
Peak unit current
A
20
37.3
37.3
Maximum unit current with resistances
A
15.3
22.8
22.8
Peak unit current with resistances
A
28.7
50.3
50.3
Dimensions (base x depth x height)
mm
550 x 330 x 1700
550 x 330 x 1700
550 x 330 x 1700
Weight
Kg
80
80
80
Refrigerant
type
R410A
R410A
R410A
MODEL
um
160
190
210
230
Dehumidification capacity
L/day
161
182
213
225
Nominal air flow
m
3
/h
1000
1200
1400
1400
Useful static head
Pa
40
40
40
40
Sound pressure
dB(A)
50
52
53
54
Hot water coil power
kW
10.4
11.9
13.3
13.3
Water coil pressure drops with valve
kPa
34
44
55
55
Electrical power supply
V/ph/Hz
230/1+N/50
230/1+N/50
400/3+N/50
400/3+N/50
Electrical heaters capacity
kW
4
4
4
4
Nominal compressor power
kW
2
2.49
3.15
3.24
Nominal compressor current
A
9.1
11.5
5.9
6.1
Nominal unit power
kW
2.1
2.62
3.31
3.4
Maximum unit power
kW
3.02
3.28
4.72
4.78
Nominal unit current
A
9.9
12.5
7.1
7.3
Maximum unit current
A
14.5
15.9
9.3
9.4
Peak unit current
A
55.8
63.8
49.8
49.8
Maximum unit current with resistances
A
31.9
33.3
18
18.1
Peak unit current with resistances
A
73.2
81.2
58.5
58.5
Dimensions (base x depth x height)
mm
750 x 330 x 1700
750 x 330 x 1700
750 x 330 x 1700
750 x 330 x 1700
Weight
Kg
140
140
160
160
Refrigerant
type
R410A
R410A
R410A
R410A
The dehumidification power is declared in the nominal point 30° C/80% RH
The currents and the absorbed powers are declared in the nominal point 30°C/80% RH
The power of the hot water coil is declared with ambient air at 30°C and water in 80°C and out 70°C
The sound pressure is measured at 1 meter in free field
In different conditions the declared values will undergo variations which can also be very important, the further away from the
nominal operating conditions.

Related product manuals