F1 DI 16 01 3 Product Description
HI 800 153 E Rev. 2.00 Page 13 of 42
3.2 Equipment, Scope of Delivery
The following table specifies the available remote I/O variants:
Designation Description
F1 DI 16 01 Remote I/O (16 digital inputs),
Operating temperature: 0...+60 °C,
for ELOP II Factory programming tool
F1 DI 16 011
(-20 °C)
Remote I/O (16 digital inputs),
Operating temperature: -20...+60 °C,
for ELOP II Factory programming tool
F1 DI 16 01
SILworX
Remote I/O (16 digital inputs),
Operating temperature: 0...+60 °C,
for SILworX programming tool
F1 DI 16 011
SILworX
(-20 °C)
Remote I/O (16 digital inputs),
Operating temperature: -20...+60 °C,
for SILworX programming tool
F1 DI 16 014
SILworX
Remote I/O (16 digital inputs),
Operating temperature: -25...+70 °C (temperature class T1),
Vibration and shock tested according to EN 50125-3 and EN 50155,
class 1B according to IEC 61373,
for SILworX programming tool
Table 4: Available Variants
3.2.1 IP Address and System ID (SRS)
A transparent label is delivered with the device to allow one to note the IP address and the
system ID (SRS for system rack slot) after a change.
IP___.___.___.___SRS____.__.__
Default value for IP address: 192.168.0.99
Default value for SRS: 60 000.200.0 (SILworX)
60 000.0.0 (ELOP II Factory)
The label must be affixed such that the ventilation slots in the housing are not obstructed.
Refer to the First Steps manual of the programming tool for more information on how to modify
the IP address and the system ID.