F1 DI 16 01 4 Start-up
HI 800 153 E Rev. 2.00 Page 27 of 42
4.3.2.1 Tab Module
The Module tab contains the following system parameters:
System parameter
Data
type
R/W Description
DI Number of
Pulsed Channels
USINT W Number of pulsed outputs (supply outputs)
Coding Description
0
No pulsed output planned for SC/OC
1)
detection
1 Pulsed output 1 planned for SC/OC
1)
detection
2
Pulsed output 1 and 2 planned for SC/OC
1)
detection
4
Pulsed outputs 1...4 planned for SC/OC
1)
detection
Pulsed outputs must not be used as safety-related outputs!
DI Pulse Slot UDINT W Pulse module slot
(SC/OC
1)
detection), set the value to 3
DI Pulse Delay [µs] UINT W
Waiting time for line control (detection of short-circuits or cross-
circuits)
DI.Error Code WORD R Error codes for all digital inputs
Coding Description
0x0001 Fault within the digital inputs
0x0002 FTT test of test pattern faulty
DO.Error Code WORD R Error code of the TO unit as a whole
Coding Description
0x0001 Error of the TO unit as a whole:
Module Error Code WORD R Module error code
Coding Description
0x0000 I/O processing, if required with errors
see other error codes
0x0001 No I/O processing (remote I/O not in RUN)
0x0002 No I/O processing during the booting test
0x0004 Manufacturer interface operating
0x0010 No I/O processing: invalid configuration
0x0020 No I/O processing: fault rate exceeded
0x0040/
0x0080
No I/O processing: configured module not
plugged in
Module SRS [UDINT] R Slot number (System Rack Slot)
Module Type [UINT] R Type of the module, target value: 0x002D [45
dec
]
1)
SC/OC (SC = short-circuit, OC = open-circuit)
Table 21: SILworX - System Parameters for Digital Inputs, Module Tab