4 Start-up F1 DI 16 01
Page 28 of 42 HI 800 153 E Rev. 2.00
4.3.2.2 Tab DI 16: DO Channels
The DI 16: Channels tab contains the following system parameters:
System
parameter
Data
type
R/W Description
Channel no. --- R Channel number, defined by default
-> Error Code
[BYTE]
BYTE R Error code of the individual digital pulsed output channels:
Coding Description
0x01 Fault in the digital output module
Value [BOOL]
->
BOOL W Output value for DO channels:
1 = output energized
0 = output de-energized
Pulsed outputs must not be used as safety-related outputs!
Table 22: SILworX - System Parameters for Pulsed Outputs, DI 16: DO Channels Tab
4.3.2.3 Tab DI 16: DI Channels
The DI 16: Channels tab contains the following system parameters.
System
parameter
Data
type
R/W Description
Channel no. --- R Channel number, defined by default
-> Error Code
[BYTE]
BYTE R Error codes for the digital input channels
Coding Description
0x01 Fault in the analog input module
0x10 Short-circuit of the channel
0x80
Intermittence between pulsed output TO and digital
input DI, e.g.,
Open-circuit
Open switch
L+ undervoltage
-> Value
[BOOL]
BOOL R Input values for the digital input channels
0 = input de-energized
1 = input energized
Pulsed
Channels
[USINT] ->
USINT W Source channel for pulsed supply
Coding Description
0 Input channel
1 Pulse of the 1st TO channel
2 Pulse of the 2nd TO channel
3 Pulse of the 3rd TO channel
4 Pulse of the 4th TO channel
Table 23: SILworX - System Parameters for Digital Inputs, DI 16: DI Channels Tab