F1 DI 16 01 4 Start-up
HI 800 153 E Rev. 2.00 Page 31 of 42
System signal R/W Description
DI Pulse Delay
[10E-6s]
[UINT]
W Waiting time for line control (detection of short-circuits or cross-circuits)
1)
SC/OC (SC = short-circuit, OC = open-circuit)
Table 24: ELOP II Factory - Digital Input System Signals
4.4.4 Pulsed Outputs F1 DI 16 01
System signal R/W Description
Mod.SRS [UDINT] R Slot number (System Rack Slot)
Mod. Type [UINT] R Type of the module, target value: 0x002D [45
dec
]
Mod. Error Code
[WORD]
R Module error code
Coding Description
0x0000 I/O processing, if required with errors
see other error codes
0x0001 No I/O processing (remote I/O not in RUN)
0x0002 No I/O processing during the booting test
0x0004 Manufacturer interface operating
0x0010 No I/O processing: invalid configuration
0x0020 No I/O processing: fault rate exceeded
0x0040/
0x0080
No I/O processing: configured module not plugged in
DO.Error Code
[WORD]
R Error code of the TO unit as a whole
Coding Description
0x0001 Error of the TO unit as a whole:
DO[xx].Error Code
[BYTE]
R Error code of the individual digital pulsed output channels:
Coding Description
0x01 Fault in the digital output module
DO[xx].Value [BOOL] W Output value for TO channels:
1 = output energized
0 = output de-energized
Pulsed outputs must not be used as safety-related outputs!
Table 25: ELOP II Factory - System Signals for the Pulsed Outputs