EasyManua.ls Logo

HIMA HIMax X-DI 64 01 - System Bus Indicators; I;O Indicators

HIMA HIMax X-DI 64 01
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
X-DI 64 01 3 Product Description
HI 801 093 E Rev. 4.00 Page 15 of 52
3.4.4 System Bus Indicators
The system bus LEDs are labeled Sys Bus.
LED Color Status Description
On
Physical and logical connection to the system bus
module in slot 1.
Green
Blinking1
No physical connection to the system bus module in
slot 1.
A
Yellow Blinking1
The physical connection to the system bus module
in slot 1 has been established.
No connection to a (redundant) processor module
running in system operation.
On
Physical and logical connection to the system bus
module in slot 2.
Green
Blinking1
No physical connection to the system bus module in
slot 2.
B
Yellow Blinking1
The physical connection to the system bus module
in slot 2 has been established.
No connection to a (redundant) processor module
running in system operation.
A+B Off Off
Neither physical nor logical connection to the sys-
tem bus modules in slot 1 and slot 2.
Table 5: System Bus Indicators
3.4.5 I/O Indicators
The LEDs of the I/O indicators are labeled Channel.
LED Color Status Description
On The related channel is active (energized).
Blinking2 Channel fault
Channel
1…64
Yellow
Off The related channel is inactive (de-energized).
Blinking2
Field fault on at least one channel or supply (e.g.,
overcurrent, etc.)
Field Red
Off No field fault displayed!
Table 6: I/O Indicators LEDs

Table of Contents

Related product manuals