4.4 Connection Variants 
This chapter describes the correct wiring of the module in safety-related applications. The 
connection variants specified here are permitted. 
4.4.1 Input Wiring 
The inputs are wired via connector boards. Special connector boards are available for 
redundantly wiring the modules. 
The supply is decoupled using diodes. This ensures that the supplies of two modules can 
supply one proximity switch if the modules are redundant to one another 
 
Connector boards X-CB 006 01 (with screw terminals) or X-CB 006 03 (with cable plug) can 
be used to perform the wiring such as described in 
Figure 12, Figure 13 and Figure 14. 
Connector Board
S+
DI+
X-DI 64 01
1
2
 
 Transmitter Supply   Digital Input 
Figure 12:  Wiring with Contact Maker or Two-Wire Proximity Switch 
 
 
 Digital Input   
Figure 13:  Wiring of a Digital Signal Source with Electrically Isolated Supply