X-DI 64 01  3 Product Description 
HI 801 093 E Rev. 4.00  Page 17 of 52 
Digital inputs 
Number of inputs (number of channels)  64 unipolar with reference pole DI- / L-, 
Non-galvanically isolated from one another 
Type of input 
Current sinking logic, 24 V, type 3 in accor-
dance with IEC 61131-2 
Rated input voltage  0...24 V 
Input voltage operating range  -3...30 V, current limiting 
2.3...2.9 mA (depending on the temperature) 
Switching point  typ. 9.4 V ± 0.8 V  (2.1 mA ± 0.3 mA) 
Refresh of measured values  
(in the user program) 
Cycle time of the user program 
Table 8:  Specifications for Digital Inputs 
 
Supply 
Number of sources  8 with 8 outputs each 
Output voltage for supply  Supply voltage - 2.5 V 
Output current for supply  100 mA for each group 
Short-circuit-proof 
Undervoltage detection 
The module monitors the supplies for undervoltage  
(< 17 VDC). 
If a fault occurs, the corresponding Supply X OK status is 
set to FALSE. 
Short-circuit of one supply  Undervoltage detection active 
The output current is pulsed < 250 mA while the supply is 
short-circuited. 
Assignment of the supply outputs 
For supplying, the supply output assigned to the input must be used! 
Supply S1+  DI1+…DI8+ 
Supply S2+  DI9+…DI16+ 
Supply S3+  DI17+…DI24+ 
Supply S4+  DI25+…DI32+ 
Supply S5+  DI33+…DI40+ 
Supply S6+  DI41+…DI48+ 
Supply S7+  DI49+…DI56+ 
Supply S8+  DI57+…DI64+ 
Table 9:  Product Data for Supply