4 Start-up X-DI 64 01
Page 34 of 52 HI 801 093 E Rev. 4.00
4.3.2 Tab: I/O Submodule DI64_01
The I/O Submodule DI64_01 tab contains the following system parameters:
Name R/W Description
This parameter cannot be changed.
Name W Module name
Name
Data
Type
R/W Description
The following statuses and parameters can be assigned global variables and used in the user program.
Background Test Error BOOL R TRUE: Background test is faulty
FALSE: Background test is free of faults
Diagnostic Request DINT W
To request a diagnostic value, the appropriate ID must be
sent to the module using the parameter Diagnostic Re-
quest (see Chapter
4.3.5 for coding details).
Diagnostic Response DINT R
As soon as Diagnostic Response returns the ID of Diag-
nostic Request (see
4.3.5 for coding details), Diagnostic
Status contains the diagnostic value requested.
Diagnostic Status DWORD R
Requested diagnostic value in accordance with Diagnos-
tic Response.
The IDs of Diagnostic Request and Diagnostic Response
can be evaluated in the user program. Diagnostic Status
only contains the requested diagnostic value when both
Diagnostic Request and Diagnostic Response have the
same ID.
Restart on Error BOOL W
Using the parameter Restart on Error, each I/O module
that has switched off permanently due to faults can be
forced to re-adopt the RUN state. To do this, set the Re-
start on Error parameter FALSE to TRUE.
The I/O module performs a complete self-test and only
enters the RUN state if no faults are detected.
Default setting: FALSE
Submodule OK BOOL R TRUE: No submodule fault
No channel faults
FALSE: Submodule fault
Channel fault (external faults included)
Submodule Status DWORD R Bit-coded submodule status (see 4.3.4 for coding details)
Supply 1 OK BOOL R The supplies are monitored for undervoltage
TRUE: The supply is faultless.
FALSE: The supply is faulty.
Supply 2 OK BOOL R Such as Supply 1 OK
Supply 3 OK BOOL R Such as Supply 1 OK
Supply 4 OK BOOL R Such as Supply 1 OK
Supply 5 OK BOOL R Such as Supply 1 OK
Supply 6 OK BOOL R Such as Supply 1 OK
Supply 7 OK BOOL R Such as Supply 1 OK
Supply 8 OK BOOL R Such as Supply 1 OK
Table 18: Tab I/O Submodule DI64_01 in the Hardware Editor