X-DI 64 01  4 Start-up 
HI 801 093 E Rev. 4.00  Page 35 of 52 
4.3.3  Tab: I/O Submodule DI64_01: Channels 
The I/O Submodule DI64_01: Channels tab contains the following parameters and 
statuses for each digital input.  
Global variables can be assigned to the statuses and parameters with -> and used in the 
user program. The value without -> must be directly entered. 
Name 
Data 
Type 
R/W  Description 
Channel no.  ---  R  Channel number, defined by default 
-> Channel Value 
[BOOL] 
BOOL  R  Boolean value of the digital input LOW or HIGH. 
-> Channel OK  BOOL  R  TRUE: Faultless channel 
The channel value is valid. 
FALSE: Faulty channel 
The input value is set to FALSE 
Ton [µs]  UDINT  W  Time on delay 
The module only indicates a level change from LOW to 
HIGH if the HIGH level is present for longer than the con-
figured time t
on
. 
Important: The maximum reaction time T
R
 (worst case) for 
this channel is extended by the delay time, since a level 
change is not detected until the delay time has expired. 
Range of values: 0 … (2
32
 - 1) 
Default setting: 0 
Toff [µs]  UDINT  W  Time off delay 
The module only indicates a level change from HIGH to 
LOW if the LOW level is present for longer than the con-
figured time t
off
. 
Important: The maximum reaction time T
R
 (worst case) for 
this channel is extended by the delay time, since a level 
change is not detected until the delay time has expired. 
Range of values: 0…(2
32
-1) 
Default setting: 0 
Test Suppression [µs]  UDINT  W 
The digital module can filter out external test impulses 
(set from HIGH to LOW for a short time) that last for the 
duration of t
Pulse
 < t
Suppression
. 
The suppression time t
Suppression
 can be configured by the 
user.  
The highest suppression time configured for a channel 
applies to all channels on the module if the suppression 
time set for the channels is greater than 0. 
Note that the duration of the I/O cycle and thus that of the 
CPU cycle is extended. 
Range of values 0...500 µs  
Default setting: 0 (deactivated for this channel) 
Sup. used  BOOL  W  Activated: The supply is used. 
Deactivated: The supply is not used. 
Default setting: Activated 
Redund.  BOOL  W  Requirement: A redundant module must exist. 
Activated: Activate the channel redundancy for this chan-
nel 
Deactivated: Deactivate the channel redundancy for this 
channel 
Default setting: Deactivated