X-DI 64 01  4 Start-up 
HI 801 093 E Rev. 4.00  Page 33 of 52 
4.3.1 Tab: Module 
The Module tab contains the following system parameters for the module: 
Name  R/W  Description 
Enter these statuses and parameters directly in the Hardware Editor. 
Name W Module name 
Spare Module  W 
Activated: The module missing in the redundancy group is not 
considered as a fault. 
Deactivated: The module missing in the redundancy group is 
considered as a fault. 
Default setting: Deactivated 
It is only displayed in the redundancy group tab! 
Noise Blanking  W 
Noise blanking performed by processor module allowed (acti-
vated/deactivated).  
Default setting: Activated 
The processor modules defers the reaction to detected tran-
sient faults until the safety time has expired. The user program 
retains its last valid process value. 
 
Name 
Data 
Type 
R/W  Description 
The following statuses and parameters can be assigned global variables and used in the user program. 
Module OK  BOOL  R  TRUE: 
Mono operation: No module faults. 
Redundant operation: At least one of the redundant modules 
is faultless (OR logic). 
 
FALSE: 
Module fault 
Channel fault (no external faults) 
The module is not plugged in. 
 
Observe the Module Status parameter! 
Module Status  DWORD  R  Status of the module 
Coding  Description 
0x00000001 Module fault 
1)
 
0x00000002 Temperature threshold 1 exceeded 
0x00000004 Temperature threshold 2 exceeded 
0x00000008 Incorrect temperature value 
0x00000010 Voltage L1+ is defective 
0x00000020 Voltage L2+ is defective 
0x00000040 Internal voltage is defective 
0x80000000 No connection to the module 
1)
 
1)
  These faults affect the Module OK status and need not 
be separately evaluated in the user program. 
 
Timestamp [µs]  DWORD  R  Microsecond fraction of the timestamp. 
Point in time at which the digital inputs were measured. 
Timestamp [s]  DWORD  R  Second fraction of the timestamp. 
Point in time at which the digital inputs were measured. 
Table 17:  Module Tab in the Hardware Editor