Monitor abnormal occurrences
11
Refer to "Analyze"( p.12) for analysis methods.
3 Set automatic saving
Move
the cursor
Displays the
[File Save] sheet
Carry out the following setting using the file saving sheet on the System screen.
Select
setting
items
Savable media is HDD and CF Card only.
When saving to the CF Card, please ensure that there
is enough capacity and the card is properly inserted.
Save to
Specify the folder to save to.
Auto Save
Set to [On].
4 Start and Stop Measurement
Press the START key.
[Trigger waiting] will be displayed until the commer-
cial power voltage satisfies the trigger conditions
(in this case, until a spontaneous blackout occurs).
When the trigger conditions are met, the trigger is
activated and measurement will start.
Data will be saved automatically to the CF card
and wait the next spontaneous blackout after finish
the measurement.
Measurement data will be recorded until the
STOP key is pressed.
[Trigger waiting]
127.2 V
-127.2 V
Trigger level
1/2 cycle
T