Error code list
© 2009 Hirschmann Automation and Control GmbH · Branch Office Ettlingen · eMail: info.ecs@hirschmann.de · www.hirschmann.com 40
24 183 19 1012e (Generic) / 2009-02-26 / Rev. 01 / rk.
Error Code Error Cause Elimination
Pressure transducer is
defective.
PDB variable for analog value
not supported
Replace pressure transducer
Setup of correct PDB variable
for analog value in DGA6.i.3
E12
Fallen below the lower
limit value in the
measuring channel
"pressure piston side"
Electronic component in the
measuring channel is defective.
Replace sensor unit
E13
Fallen below lower limit
value in the measuring
channel "pressure rod
side"
refer to E12 refer to E12
E14
Fallen below lower limit
value in measuring
channel "force"
Force transducer defective
Electronic component in the
measuring channel is defective.
Replace force transducer
Replace sensor unit
Angle potentiometer defective
PDB variable for analog value
not supported
Replace angle sensor
Setup of correct PDB variable
for analog value in DGA6.i.3
E15
Fallen below lower limit
value in measuring
channel "angle main
boom"
Electronic component in the
measuring channel defective.
Replace sensor unit
Angle potentiometer defective Replace angle sensor
E16
Fallen below lower limit
value in measuring
channel "angle 2"
Electronic component in the
measuring channel defective.
Replace sensor unit
Length potentiometer defective Replace length sensor.
E17
Fallen below lower limit
value "length telescope I
(+II)"
Electronic component in the
measuring channel defective
Replace sensor unit
E18
Front outrigger
overloaded
Front outrigger overloaded
Cable between the central unit
and the slewing angle sensor
defective or loose. Water inside
the plug of the angle sensor
1-cannel slew sensor min. value
DGA 11.5.7 <> 0
Check cable as well as plugs,
replace, if need be.
move to allowed slew range
Slewing angle potentiometer is
defective
Replace slewing angle sensor
E1A
Fallen below lower limit
value in measuring
channel "slewing angle
1".
slew below allowed
range
Electronic component in the
measuring channel defective
Replace sensor unit
E1B
Fallen below lower limit
value in measuring
channel "slewing angle
2"
refer to E1A
refer to E1A
E1C
Fallen below lower limit
Angle potentiometer defective Replace angle sensor