61
7.3 EMC and immunity
EMC interference
emission
Standard
applications
Navy applications Railway
applications
(trackside)
Substation
applications
Radiated emission
EN 55032 Class A Class A Class A Class A
GL Guidelines EMC 1
FCC 47 CFR Part 15 Class A Class A Class A Class A
EN 61000-6-4 Fulfilled Fulfilled Fulfilled Fulfilled
Conducted emission
EN 55032 DC supply connection Class A Class A Class A Class A
GL Guidelines DC supply connection EMC 1
FCC 47 CFR Part 15 DC supply connection Class A Class A Class A Class A
EN 61000-6-4 DC supply connection Fulfilled Fulfilled Fulfilled Fulfilled
EN 55032 Telecommunication connections Class A Class A Class A Class A
EN 61000-6-4 Telecommunication connections Fulfilled Fulfilled Fulfilled Fulfilled
EMC interference
immunity
Standard
applications
Navy applications Railway
applications
(trackside)
Substation
applications
Electrostatic discharge
EN 61000-4-2
IEEE C37.90.3
Contact discharge ±4kV ±6kV ±6kV ±8kV
EN 61000-4-2
IEEE C37.90.3
Air discharge ±8kV ±8kV ±8kV ±15kV
Electromagnetic field
EN 61000-4-3 80 MHz ... 3000 MHz 10 V/m 10 V/m max. 20 V/m 10 V/m
IEEE 1613 80 MHz ... 1000 MHz 35 V/m
Fast transients (burst)

Table of Contents