Part Optional function
Indivi
dual
settin
g
Settings
Condition
setting
Description
bb
Cooling temperature offset O
00
Standard
setting. No
offset
This function is used to obtain longer
cooling periods.
01
Selected
temperature
-1 °C
02
Selected
temperature
-2 °C
bC
Not used –
00 Not used –
01
Used as setting
for conditions
00
–
bd
Not used –
00 Not used –
01
Used as setting
for conditions
00
–
bE
Not used –
00 Not used –
01
Used as setting
for conditions
00
–
C1
Not used –
00 Not used –
01
Used as setting
for conditions
00
–
C2
Not used –
- -
permane
nt
Not used –
C3
Not used O
00 Not used –
01
Used as setting
for conditions
00
–
C4
Not used O
00 Not used –
01
Used as setting
for conditions
00
–
C5
Static pressure selection O
00 Not available
This function is used to increase the fan
speed on the indoor ducted units.
01 High speed 1
2
02 High speed 2
2
C6
Fan speed increase O
00 Not available This function is used to increase the fan
speed when the thermostat reaches the
set temperature in heating with function
C5.
01 Available
C7
Cancellation of the forced
compressor operation for
at least three minutes
O
00 Not available
Cancels function b3.
01 Available
6 Optional functions
199
SMGB0063 rev. 1 - 10/2010