Part Optional function
Indivi
dual
settin
g
Settings
Condition
setting
Description
d1
Power on/off 1 O
00 Not available
This function stores the settings of the unit
in the event of a cut in the electric power
supply. The unit is restarted when the
power is re-established.
01 Available
d2
Not used X
- -
permane
nt
Not used –
d3
Power on/off 2 O
00 Not available This function is used to restart the unit after
a cut in the power supply lasting for more
than 2 seconds.
01 Available
d4
Cooling air temperature
drop prevention.
O
00 Not available This function changes the cooling
operating conditions to avoid cold
draughts.
01 Available
d5
Heating air temperature
drop prevention.
O
00 Not available This function prevents a drop in the air
temperature by decreasing the fan speed,
apart from the settings on the remote
control.
01 Available
d6
Room temperature control
for energy saving
O
00 Not available This function saves energy when the
outdoor temperature is lower than the air
conditioning charge.
01 Available
d7
Not used O 00-07
Not used. Used
as setting for
conditions 00
–
E1
Econofresh: Outdoor
cooling mode
O
KPI:
This function is used to set the ventilation
mode of the ventilation unit with energy /
heat recovery
00
Automatic
ventilation
01
Ventilation with
total heat
exchanger
02
Ventilation with
bypass (no total
heat exchange)
KPI: ventilation mode
Econofresh kit
00 Not available
01/02
Outdoor cooling
mode (All-
Fresh)
E2
Increased air supply
volume
O
00 Not available
This function is used to increase the air
supply volume in the room.
01 Available
E3
Not used O
00 Not used
–
01
Used as setting
for conditions
00
6 Optional functions
201
SMGB0063 rev. 1 - 10/2010