Loading...
bC – Not used
bd – Not used
bE – Not used
C1 – Not used
C2 – Not used
C3 – Not used
C4 – Not used
C5 – Static pressure selection
The fan speed increase selection function is only available for RCI and RCD units. It is used to increase the fan speed on
the indoor ducted units.
N O T E
In the case of RPI units, this setting is used to select the static pressure.
Settings
Condition setting
00 Not available
01 High speed 1
2
02 High speed 2
2
C6 – Fan speed increase
The fan speed increase selection function is only available for RCD units. This function is used to increase the fan speed
when the thermostat reaches the set temperature in heating with function
N O T E
The fan speed does not increase when the thermostat is switched off with the function setting (C5)
Settings
Condition setting
00 Not available
01 Available
C7 – Cancellation of the forced compressor operation for at least three minutes
This function is used when b3 – forced compressor operation for at least 3 minutes is to be cancelled.
N O T E
In the case of SET-FREE units, the forced compressor operation for at least 3 minutes described (b3) is the standard
function.
Settings
Condition setting
00 Not available
01 Available