Remove the louver in line with the instructions given in chapter Removal of the air outlet grille, see on page 317.
Open the air inlet grille as indicated in chapter Removal of the air filter, see on page 316.
Remove the lower panel and drain pan in line with the instructions given in chapter Removal of the thermistors from the
liquid and gas pipes, see on page 319.
Remove the partition plate after removing the set screws.
Remove  the  fan  securing  cover  after  removing  the  two  screws
located on the left and right of the partition.
Fit the drain pan and the lower panel in the opposite order of the
instructions.
Cleaning the indoor unit
  N O T E
Wear gloves to avoid injuries caused by the heat exchanger fins.
Place a vinyl sheet around the electrical components except the
drain pan to protect them from splashed cleaning water.
Secure the motor panel using adhesive tape.
Clean the  dust  from  the  inner surface  of  the  heat  exchanger  by
brushing  it  downwards.  Collect  all  of  the  dust  in  a  bucket  or  a
cardboard box.
Hang the cleaning water manifold from the indoor unit.
Insert the nozzle of the pressurised water gun into the hole in the
cleaning water manifold. Start the water pump and clean the heat
exchanger of any dust.
After cleaning, spray and remove all remains of water.
  N O T E
1 Set the pressure of the water pump so as not to damage the funs.
2 Any cleaning water left behind will rust the fins. Set the pump pressure to between 2.5 and 5 kg/cm
3
 to protect
the fins.
After cleaning, fit the drain pan by lowering the rope.
Dry the remains of any water on the indoor unit.
12 Maintenance notes
393
SMGB0063 rev. 1 - 10/2010
12