7-1
Chapter 7 Specifications
7.1 400V class specifications
Applicable motor capacity
(4 poles)(kW)
Overload current
rating *1)
Three-phase(3 wire)380 to 460V (Corresponding to the incoming voltage)
Rated input
current(A)
*2)
Control power supply : Single-phase supply 380 to 460V (Permissible AC voltage 323 to 506) ,
50Hz(allowable variation range: 47.5-52.5Hz)/60Hz (allowable variation range:57-63Hz)
Main circuit power supply: Three-phase(3 wire) 380to 460V (Permissible AC voltage 323 to 506) ,
50Hz(allowable variation range: 47.5-52.5Hz)/60Hz (allowable variation range:57-63Hz)
Power supply
capacity
(kVA) *3)
Carrier frequency variation
*4)
Internal BRD circuit (external discharge resistor value)
External regenerative braking unit
Minimum resistance
value(Ω)
*1) Electronic thermal protection is accordance to derating.
*2) The rated input current is the value when the drive is operated in the rated output current. The value of the impedance at the supply side changes
due to the wiring, breaker, input reactor, etc.
*3) The power supply capacity is the value of the rated output current at 440V. The value of the impedance at the supply side changes due to the wiring,
breaker, input reactor, etc.
*4) It is recommended to set the carrier frequency settings [bb101]/[bb201] equal or greater than the (maximum output frequency x 10)Hz.
For induction motor IM, it is recomended to set the carrier frequency to 2 kHz or more except V/f control. For synchronous motor (SM)/Permanent
magnet motor (PMM), it is recomended to set the carrier frequency to 8 kHz or more.
*5) Usually an external regenerative braking unit is required. However, with an optional built –in chopper braking ciruit and external discharge resistor
can eliminate a external regenerative unit. The built-in chopper braking circuit is offered by order. In order to purchase, contact to the nearest sales
office
*6) The key height of keypad are exclued from dimensions. When an option is connected, the depth is increased. Refer to the each optional instruction.