2-7
2.5 Wiring of the main circuit
Wire the main circuit of the inverter.
The following illustration shows the power supply and
wiring connections to a motor only.
Open a terminal block cover to wire the terminal block in
the main circuit.
Explanation of main circuit terminal block
The screw size may vary depending on terminal. Refer to Page
2-8/2-9 for the size of the terminal screw for the power line cable
while for other terminals, refer to the drawings of the wiring on
Page 2-11 or later.
The tables on Page 2-8/2-9 list the specifications of cables, crimp
terminals, and terminal screw tightening torques for reference.
Connect to the AC power supply. Leave these terminals unconnected
when using a regenerative converter(HS900A series).
Connect a Three-phase motor.
DC choke
connection terminal
Remove the PD-P jumper from terminals, and connect the optional DC
choke for power factor improvement.
External chopper
braking resistor
connection terminal
Connect the optional external braking resistor. See “Chapter 7
Specifications” for built-in braking circuit inverter models.
Regenerative braking
unit connection
terminal
Connect the optional regenerative braking unit.
This serves as a ground terminal for the inverter chassis to ground.
Connect 400V class models to Type-C grounding.
Earth-leakage
circuit breaker
Three-phase
AC power
supply
Control circuit
power supply
Type-C grounding
(400 V class model)
Main circuit
terminal section
400V class:
380 to 460Vac