5-1
Chapter 5
Troubleshooting
Chapter 5
Troubleshooting
5.1 Error events
Next are the descriptions of the basic errors that may
occur. For more information, contact to your supplier or
local Hitachi distributor or service station .
Trip event screen
Error events
Code
Details
Corrective actions
Related parameter
E001
By the load and the operating
conditions, overcurrent has
occurred
If the acceleration is fast, increase the acceleration time
[AC120]
Use the overcurrent suppression function
[bA120]
Use the overload restriction function
[bA122]
Use the overcurrent retry function
[bb-22]
In order to stabilize the control, adjust the constant
[HA-01]
E005
E039
By the load and the operating
conditions, current has
increased.
If the acceleration is fast, increase the acceleration time
[AC120]
Use the overload restriction function
[bA122]
If the motor sound is abnormal, in order to stabilize the
control, adjust the constant
[HA-01]
E006
Braking resistor use is limited.
If the deceleration is fast, increase the deceleration time
[AC122]
Reselection of the braking resistor is necessary
[bA-60]
E007
Internal voltage has increased
Insufficient capacity of the
inverter
If the deceleration is fast, increase the deceleration time
[AC122]
Use the overvoltage suppression functions
[bA140][bA146]
Use the overvoltage retry function
[bb-23]
Use a braking option
-
E008
E011
Main CPU abnormality
Carry out counter measures for the inverter noise
-
Consecutive errors may cause a failure
-
E009
Main circuit supply has drop
To disable the undervoltage error, change setting
[bb-27]
Use the undervoltage retry function
[bb-21]
E010
Current detector abnormality
Carry out counter measures for the inverter noise
-
Consecutive errors may cause a failure, replacement of
the components is necessary
-
E012
[EXT] input terminal is ON
Check the signal status of the input terminal
[dA-51]
Check if there are no operations by communication or
programme
-
E013
[USP] input terminal is ON if at
the start-up, the RUN command
was issued right at the start up
Make sure that an operation command is not introduced
at the time of turning ON the inverter
[dA-51]

Alarm lamp
is blinking