5-1
Chapter 5
Troubleshooting
5.1 Error events
Next are the descriptions of the basic errors that may
occur. For more information, contact to your supplier or
local Hitachi distributor or service station .
■Trip event screen
■Error events
・By the load and the operating
conditions, overcurrent has
occurred
・ If the acceleration is fast, increase the acceleration time
・Use the overcurrent suppression function
・Use the overload restriction function
・Use the overcurrent retry function
・In order to stabilize the control, adjust the constant
・By the load and the operating
conditions, current has
increased.
・ If the acceleration is fast, increase the acceleration time
・Use the overload restriction function
・If the motor sound is abnormal, in order to stabilize the
control, adjust the constant
・Braking resistor use is limited.
・If the deceleration is fast, increase the deceleration time
・Reselection of the braking resistor is necessary
・Internal voltage has increased
・Insufficient capacity of the
inverter
・If the deceleration is fast, increase the deceleration time
・Use the overvoltage suppression functions
・Use the overvoltage retry function
・Carry out counter measures for the inverter noise
・Consecutive errors may cause a failure
・Main circuit supply has drop
・To disable the undervoltage error, change setting
・Use the undervoltage retry function
・Current detector abnormality
・Carry out counter measures for the inverter noise
・Consecutive errors may cause a failure, replacement of
the components is necessary
・[EXT] input terminal is ON
・Check the signal status of the input terminal
・Check if there are no operations by communication or
programme
・[USP] input terminal is ON if at
the start-up, the RUN command
was issued right at the start up
・Make sure that an operation command is not introduced
at the time of turning ON the inverter