Element Optional function
Individual
setting
Settings Setting conditions Description
F4 Automatic reset time X
00 30 minutes (factory setting)
This function sets the automatic
reset time delay for function F3.
01 15 minutes
02 60 minutes
03 90 minutes
F5
Automatic reset temperature
for cooling
X
19 19°C
This function denes the default
temperature set point for the
automatic reset function F3 in
FAN/COOL/DRY modes.
20 20°C
21 21°C
·
·
·
·
·
·
24 24°C
25 25°C (factory setting)
26 26°C
·
·
·
·
·
·
28 28°C
29 29°C
30 30°C
F6
Automatic reset temperature
for heating
X
17 17°C
This function denes the default
temperature set point for the
automatic reset function F3 in
HEAT mode.
18 18°C
·
·
·
·
·
·
20 20°C
21 21°C (factory setting)
25 25°C
·
·
·
·
·
·
28 28°C
29 29°C
30 30°C
F7
Prevention of operation
stoppage due to wrong
operation of the remote
controller
X
00 Function disabled (factory setting)
Operation is stopped by
pressing the run/stop switch for
3 seconds.
01 Function enabled
F8
Lock function for operation
mode selection
X
00 Function disabled
This function is used to prevent
changes to the operation mode.
01 Function enabled (factory setting)
F9
Lock function for temperature
setting
X
00 Function disabled
This function is used to prevent
changes to the temperature
setting.
01 Function enabled (factory setting)
FA
Lock function for fan speed
selection
X
00 Function disabled
This function is used to prevent
changes to the fan speed.
01 Function enabled (factory setting)
Fb
Lock function for swing louver
operation
X
00 Function disabled
This function is used to prevent
changes to the automatic louver
operation.
01 Function enabled (factory setting)
SERVICE & INSTALLATION MENU
PMML0565 rev.1 - 04/2022
48