Element Optional function
Individual
setting
Settings Setting conditions Description
FC
Lower limit of setting
temperature for cooling
(Minimum value of setting
temperature allowed in
cooling)
X
00
Function disabled
19°C is the standard minimum set point
(factory setting)
This function denes the lowest
temperature setting value for
FAN/COOL/DRY modes.
01 +1°C (Lower limit 20°C)
02 +2°C (Lower limit 21°C)
03 +3°C (Lower limit 22°C)
·
·
·
·
·
·
08 +8°C (Lower limit 27°C)
09 +9°C (Lower limit 28°C)
10 +10°C (Lower limit 29°C)
Fd
Upper limit of setting
temperature for heating
(Maximum value of setting
temperature allowed in
heating)
X
00
Function disabled
30°C is the standard maximum set point.
(factory setting)
This function denes the highest
temperature setting value for
HEATING mode.
Models:
RPF(I)-FSN2E
up to 20°C (FC=10)
01 -1°C (Upper limit 29°C)
02 -2°C (Upper limit 28°C)
03 -3°C (Upper limit 27°C)
·
·
·
·
·
·
10 -10°C (Upper limit 20°C)
11 -11°C (Upper limit 19°C)
12 -12°C (Upper limit 18°C)
FE Not used -
00
- Use at 00 conditions01
02
FF Not Used O
00
- Use as 00 conditions
01
H1 Not used
00
- Use at 00 conditions
01
H2
Indication of hot start
(No Indication of operation
limitation)
X
00 Displayed
This function is used to display
or hide the automatic control
indication.
Models:
RPF(I)-FSN2E
Not available, use at 00
conditions
01 Hidden
H3 Not used
00
- Use at 00 conditions
01 / 02
H4 Not Used
00 -
Use at 00 conditions
01 -
J1 Not used -
00
- Use at 00 conditions
01
J2 Not used -
00
- Use at 00 conditions
01
J3 Colour of the run indicator X
00 Green (factory setting)
01 Red
EN
SERVICE & INSTALLATION MENU
PMML0565 rev.1 - 04/2022
49