Element Optional function
Individual
setting
Settings Setting conditions Description
J4
Override of Start/Stop
prohibition at the remote
controller
X
00 Start/Stop allowed (Factory setting)
When there is a remote control
prohibition from a central control
device, this function overrides
this prohibition allowing the
operation of the Run/Stop
button of the remote control
switch.
Models:
RPF(I)-FSN2E
Not used. Use at 00 conditions
01
Start/Stop not allowed
! DANGER
Blocking of Start/Stop shall never be set
due to safety concerns.
02 Only Stop allowed
J5 Not used -
00
- Use at 00 conditions
01
J6 Error Sound X
00 Once
To produce a sound when unit is
on alarm.
01 Continuous
J7 Not used
00
- Use at 00 conditions
01
J8 Eco-operation
(7)
X
00 Function disabled (factory setting)
When the unit is restarted by
the remote control switch, the
temperature automatically
changes to the setting
temperature of “F5” or “F6”.
Models:
RPF(I)-FSN2E
Not available, use at 00
conditions
01 Function enabled
J9 Not used -
00
- Use at 00 conditions
01
JA
Display of "Simple
maintenance display" menu
O
00 Function disabled (factory setting)
Enables the “Simple
maintenance display” menu.
Models:
RPF(I)-FSN2E
Not available, use at 00
conditions
01 Function enabled
Jb Not used
00
- Use at 00 conditions
01
SERVICE & INSTALLATION MENU
PMML0565 rev.1 - 04/2022
50