EasyManua.ls Logo

Hitachi PC-ARFG-E - Software version check; LCD check

Hitachi PC-ARFG-E
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1 Select “Service Menu” on the Service & Installation screen
and press “OK”.
2 Select “Power Saving Details Setting” and press “OK”.
3 Select “Capacity Control” and press “OK”.
4 Press “ ” or “ ”.
The items “Control” ↔ “Sav: LOW” ↔ “Sav: MED” ↔
“Sav: HIGH” are displayed in order.
Press “ ” to move to “Change level”.
Change the Control Method
Select “Control”and press”OK”.
Press “ ” or “ ” to select the item to set and press “OK”.
It changes between “Peak Cut Control” and “Moderate Control”.
Press “ ” to return to Step 4.
Change the power savings level
Select “Sav: LOW (MED/HIGH)” and press “OK”. Press “ ” or
” to set the level.
→ The level changes as follows: [100%] ↔ [90%] ↔ [80%] ↔
[70%] ↔ [60%] ↔ [50%] ↔ [40%] ↔ [0%].
After setting, select “
OK
” and press “OK” and it returns to Step3.
Change level
Press “ ” or “ ” to select the item to set and press “OK”.
It changes in the order of “LOW → MED → HIGH” ↔ “LOW
only” ↔ “MED only” ↔ “HIGH only”.
Press “ ” to return to Step 3.
? NOTE
For the sub remote controller, only the level switching order can be set.
If some settings are changed in the “Power Saving details Settings”
menu, the power saving function using the related control mode is
automatically set to OFF in the Function menu. It is necessary to set
it ON again manually once the settings are done.
The cooling/heating capacity can decrease when using the “Power
Savings” function.