3 Features and benets
Centralised remote controls
TCGB0106 rev.0 - 12/2014
4040
3.2  Centralised remote controls
3.2.1  PSC-A64GT
The central station (PSC-A64GT) is connected to H-LINK system and used for the central control and monitoring of the air 
conditioners.
PSC-A64GT: Touch Screen Central Station
•  Touch Screen Central Station with attractive design.
•  Monitoring of Operating Conditions for Block/Groups.
•  Up to 4 blocks with a maximum number of 16 groups per block. Therefore, up to 64 groups can be created.
•  A maximum number of 16 indoor units by group is allowed, with a maximum of 160 indoor units per H-LINK II system.
•  Up to 8 central stations EZ (PSC-A64GT) can be connected to a H-LINK.
•  Compatible with all RCS and Timers
•  The main control functions are: Run/Stop Operation Mode Change, Fan Speed Control, Swing Louver Direction Con-
trol, Temperature Setting, Permitting/Prohibiting Operation by Remote Control Switch.
•  Optional Functions:
 - Schedule Operation (Run/Stop and Temperature Setting) for Block/Group
 - Run/Stop, Emergency Stop and Demand Function by External Input
 - Run an Alarm Output by External Output
 - Control Exception Function of All Run/Stop Command for Selected Groups
 - Control Exception Function of All Run/Stop Command for Selected Groups by External Input
 - Indication and Calculation of Unit Accumulated Operation Time of Each Group
 - Indication of Alarm History Record
 - Registering Name of Blocks and Groups
 - Registration and Indication of Service Contact Information
•  Operation modes can be selected as Normal Operation or Run/Stop Only.
•  A system conguration example is shown below:
 
  
 
Max 8 units in the same H-LINK are available. 
(Set RSW1 correctly)
Max. 64 remote control group and max 160 indoor units are available.
 
(For H-LINK II only)
Central station
 
(PSC-A64GT)
Wiring for remote control switch
Controlled by central station 
(Remote control group)
Group
Group
Group
Group
H-LINK 
transmission 
wiring
Without 
 
transmission 
wiring
With 
 
transmission 
wiring
Without 
 
remote 
control 
switch
Without 
 
remote 
control 
switch