6  Building air conditioning controls
CSNET Manager LT/XT
TCGB0106 rev.0 - 12/2014
563563
6
Description of parameters
To use this option, you have to set the parameters shown in the Auto Cool/Heat operation panel. After that, if unit is 
working in Auto Cool/Heat mode, you can see the status of this operation on the status zone of the panel.
The Auto Cool/Heat panel shown corresponds to the cooling circuit of the indoor unit selected in the table of indoor units, 
as shown in the example.
You should adjust the following parameters:
•  Unit conguration
 - Master unit: Field for selecting the method CSNET will use to calculate the temperature difference.
 -
 (Marked): CSNET will only use this unit to calculate the temperature difference and decide the change, not 
taking into account the other units connected to the same 2-tube cooling circuit.
 -
 (Not marked): CSNET will use the average temperature difference of all the indoor units connected to the 
same 2-tube cooling circuit.
 CAUTION
When this method is used (marked), the following outdoor unit option cannot be used: “control of indoor unit fan speed” (during operation 
with the thermostat deactivated in heat mode, the indoor fan stops for 6 minutes and operates for 2 minutes). If it is used, the decision of 
when to change will not always be correct (if it is measured during the deactivation cycle of 6 minutes).
 - Select input data:  eld  for  selecting  what  inlet  temperature  CSNET  should  use  to  calculate  the  temperature 
difference if an optional remote temperature sensor is connected in THM4 of the PCB of the indoor unit or if there is 
RCS remote sensor. When there are selected a combination of different sensor it will calculate the average between 
them. When nothing is selected, it is forced to use the Tin value.
 - Minutes between change mode: The time which must elapse between the last change of operation mode to the 
next change.
 - Pre set adjustment: 20 min.
 - 10 min steps.
 - 20 min... 60 min margin.