The sound operation can be adjusted by selecting the control function number.
Control function number Operating sound (targeted value)
Outdoor unit capacity (specification
ratio)
No setting Catalogue value 100%
11 (Low noise level setting 1) Catalogue value -2 dB(A) 80%
12 (Low noise level setting 2) Catalogue value -5 dB(A) 60%
13 (Low noise level setting 3) Catalogue value -8 dB(A) 40%
• Short-circuit terminals 1 and 2 (input 3) of CN18 to set the low noise setting.
N O T E
• The capacity of the outdoor unit will decrease because the compressor frequency and the outdoor unit fan
frequency necessarily decreases. The range of operation may be restricted.
• In some cases, the sound operation (key values) can be temporarily higher than the values in the table.
a 3-pin connector
b Outdoor unit PCB1
c Control circuit
d Power source
X1 Auxiliary relay
SS3 Demand current stoppage
Example: Low noise setting 2 during night time only:
A Capacity
B Operating sound
C Daytime schedule
D Nighttime schedule
E Input terminal short-circuited
F Catalogue value [dB(A)]
G Catalogue value -5 dB(A)
6.2.2 External output function setting
The following signals can be received by the outdoor unit PCB.
6 Optional functions
120