Control device
Cooling
Heating
Heat recovery
Defrost
Purpose Contents Purpose Contents Contents
High and low
pressure shut-off
valve (SVG
)
Shut-off of high
and low pressure
in the cycle during
stoppage
Compressor
operating: ON
Compressor
stopped: OFF
Shut-off of high
and low pressure
in the cycle during
stoppage
Compressor
operating: ON
Compressor
stopped: OFF
Open
Pd: Discharge pressure.
Ps: Suction pressure.
SH: Superheat.
SC: Supercooling.
TdSH: Superheat of discharge gas temperature.
5.1.2 Compressor operation control
¿ Compressor rotation control
The compressor rotation control is carried out to match its operation time in each of the outdoor units.
This control is carried out during the Thermo-OFF of the outdoor unit.
In case of switch-OFF or
Thermo-OFF after 120 minutes of operation, the inverter compressor with the shortest operation
time will be preferably turned on.
N O T E
In order to carry out this function, at least two outdoor units are required.
The operating sequence of the compressor rotation is described below.
RAS-20FSXN
Outdoor unit 1 Outdoor unit 2
-I-
Last time 1 2
Currently 2 1
Next time 1 2
-I- Inverter compressor
RAS-(22-26)FSXN
Outdoor unit 1 Outdoor unit 2
-I- -C- -I-
Last time 1 3 2
Currently 2 3 1
Next time 1 3 2
-I- Inverter compressor
-C- Constant compressor
5 Control system
89
SMGB0065 rev. 1 - 12/2010