2.1.6 Foundation and anchorage of outdoor unit
¿ Foundations
N O T E
All measurements are in mm.
A. Mortar housing ø100 x 150 (square x depth).
B. Drainage 100 x 20 (width x depth).
C. Anti-vibration insulation material.
D. Refrigerant pipes.
The
foundations
for the installation of the outdoor unit must be more
than 150 mm above ground level.
The foundations require perimeter drainage to help drain condensation.
When a system of condensation drainage pipes is required for the outdoor unit, the genuine accessory DBS-TP10A should
be used. Do not fit drainage pipes or collection trays in cold climates, as they could freeze and break.
D A N G E R
Drainage must
not take place in areas frequented by pedestrians. In low temperatures, the drainage water could
freeze and lead to falls.