Function setting
No. Setting item
7-segment display
Contents
SEG2 SEG1
1
Indoor unit fan control during the
Thermo-OFF in heating mode
FA
00 No setting
01
Forced connection and disconnection on the indoor unit fan (2 minutes ON / 6
minutes OFF).
2 Night-shift ni
00 No setting
01 Setting of night-shift
3
Cancellation of the outdoor ambient
temperature limit.
GS
00 No setting
01 For heating
02 For cooling
03 For cooling/heating
4
Defrost for cold area (change in the
defrost condition)
Jo
00 No setting
01 Defrost operation condition 2
5 SLo (fan speed) Defrost setting bJ
00
Stopping the Indoor unit fan when the heating operation is turned on during the
defrost operation
01 Indoor unit SLo fan operation during the defrost operation
02 Indoor unit SLo fan operation when the heating operation is activated
03
Fan operation when the heating operation is activated/Operation of the indoor
unit SLo fan during defrost operation
6 Cancellation of the hot start HT
00 Hot start available
01 Cancellation of the hot start
7 Priority capacity mode nU
00 No setting
01 Change in the maximum frequency limit value
02 Change in the current limit value
03 Change in the maximum frequency limit value and the current limit value
8
Target value of the compressor
frequency for cooling
Hc
00 Initial setting (Targeted value of the Ps evaporating temperature 7 °C)
01 Targeted value (2 °C)
02 Targeted value (3 °C)
03 Targeted value (4 °C)
04 Targeted value (5 °C)
05 Targeted value (9 °C)
06 Targeted value (10 °C)
07 Targeted value (11 °C)
08-09 Not prepared (If set, the setting item will be ignored by the control PCB)
9
Target value of the compressor
frequency for heating
Hh
00 Initial setting (Targeted value of the Ps 2.85 MPa)
01 Targeted value (2.60 MPa)
02 Targeted value (2.75 MPa)
03 Targeted value (2.80 MPa)
04 Targeted value (2.82 MPa)
05 Targeted value (2.88 MPa)
06 Targeted value (2.90 MPa)
07 Targeted value (2.95 MPa)
08-09 Not prepared (If set, the setting item will be ignored by the control PCB)
6 Optional functions
128
SMGB0065 rev. 1 - 12/2010