Alarm code
C2
Incorrect setting of the indoor unit connection number (CH unit).
The unit no., alarm code ("35") and the unit code are alternately indicated in the temperature setting section of the indoor
unit connected to the CH unit.
LED (LED4, 5, 6) in PCB(1) of the CH unit flashes.
* < Heat recovery system (3 pipes) >
This alarm is indicated when nine or more indoor units are connected to the CH unit.
No
Yes
Are 9 or more indoor units
connected to CH unit?
Correctly connect the wiring
and reset
the power supply.
Failure of PCB(1) in CH unit
PCB1: Control PCB in Outdoor Unit
PCB(1): CH Unit PCB
Alarm code "C2" will be indicated when the units are connected as follows.
Outdoor Unit
(Ref. Cycle Group: 1)
CH Unit
Indoor Unit 1
(Ref. Cycle Group: 1)
Indoor Unit 2
(Ref. Cycle Group: 1)
Indoor Unit 3
(Ref. Cycle Group: 1)
Indoor Unit 9
(Ref. Cycle Group: 1)1)
8 Troubleshooting
236