12.1 Checking the power source and the wiring connection
Check the following items in the case of abnormal operation:
No. Check item Procedure
1 Is the breaker of the fuse cut out? Check the secondary voltage of the breaker and the fuse by means of a tester.
2
Is the secondary power source on
the transformer correct?
Disconect the secondary side of the transformer and check the voltage by
means of a tester.
circuit and voltage
Primary side
220V or 240V
Indoor Unit
transformer
Secondary
side
12V
12V
3
Is the wiring loosened or
incorrectly connected?
Check the wiring connection on the PCB.
Thermistor connectors
Connector of the remote control cable
Cobbector of the transformer
Each connector in a high-voltage circuit
Check the connectors according to the electrical wiring diagram.
12 Maintenance notes
348
SMGB0065 rev. 1 - 12/2010