N O T E
Only the DIP DSW1, DSW2 and DSW4 switches can be set while the voltage supply is connected.
The
symbol
“■” indicates the position of the DIP switches. The figures show the position of the DIP switch once
the position setting has been completed.
With the DSW4 switch, the unit starts or stops after 10 to 20 seconds of the switch being activated.
Record the number of the outdoor unit to tell it apart from others during service and maintenance operations
in this area:
PSW1
PSW2
PSW3PSW5
PSW4
PSW: Pushswitch on PCB1
PSW1: Enter.
PSW2, 3, 4 and 5: for checking.
DSW1, RSW1: refrigerant cycle number setting
Setting required.
Setting before RSW1 supply: 0.
Setting before DSW1 supply: 0 (digit of tens).
Set each outdoor unit number on each refrigerant cycle.
Outdoor and indoor units belonging to the same refrigerant cycle: set the
same cycle number in the outdoor and indoor units (indoor units: DSW5
and RSW2).
DSW1, RSW1: setting example for refrigerant cycle number 25
Maximum refrigerant cycle number setting: 63.
DSW2: capacity setting
Setting not required.
DSW3
Setting not required.
DSW4: test run and service settings
Setting required.
A: setting before supply.
B: refrigeration test run.
C: heating test run.
D: forced compressor stoppage.
4 Electrical wiring
79
SMGB0065 rev. 1 - 12/2010
4