S1 series standard inverter 
-107- 
Detailed parameter description 
Note: Source 1-6, 100% relative to the max. 
frequency 
Source of upper 
limit frequency 
setup of reverse 
rotation in torque 
control 
0: Keypad (P03.17)   
1: AI1     
2: AI2     
3: AI3 (up to 2.2kW) 
4: Pulse frequency HDI/HDIA   
5: Multi-step   
6: Modbus communication   
7 - 12: Reserved 
Note:  Source  1-6,  100%  relative  to  the  max. 
frequency 
Keypad limit 
value of upper 
limit frequency of 
forward rotation in 
torque control 
This function code is used to set frequency limit. 
100% corresponds to the max. frequency. P03.16 
sets the value  when P03.14=1;  P03.17 sets the 
value when P03.15=1. 
Setting  range:  0.00Hz–P00.03  (Max.  output 
frequency) 
Source of upper 
limit setup of the 
torque during 
motoring 
0: Keypad (P03.20)   
1: AI1   
2: AI2     
3: AI3 (up to 2.2kW) 
4: Pulse frequency HDI/HDIA   
5: Modbus communication     
6 - 11: Reserved 
Note: Source 1-5, 100% corresponds to three 
times of rated motor current 
Source of upper 
limit setup of 
brake torque 
0: Keypad (P03.21)   
1: AI1   
2: AI2   
3: AI3 (up to 2.2kW) 
4: Pulse frequency HDI/HDIA   
5: Modbus communication     
6 - 11: Reserved 
Note:  Source  1-5,  100%  corresponds  to  three 
times of rated motor current. 
Set upper limit of 
the torque when 
This function code is used to set torque limit. 
Setting range: 0.0–300.0% (rated motor current)